DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

SIL855160 View Datasheet(PDF) - celduc-relais

Part Name
Description
Manufacturer
SIL855160 Datasheet PDF : 4 Pages
1 2 3 4
celpac®
S/CLP/SIL855160/B/21/04/2004
page 3 / 4/GB
Thermal specifications .
Current according ambient temperature :
Ø The curve "1" gives the limits of the product.
The temperature reached are acceptable for the com-
ponents. These values are in compliance with most of
SSRs manufacturers.
In a cabinet with a minimum of ventilation or a non
permanent current, these values are correct.
Ø The curve "2" gives the limits of the product
according to EN60947-4-3 with a maximum rise
temperature of 50°C (@40°C) for a permanent
working and in air calm ( test during 8 hours).
Ø For a non permanent current, you can calcule
the average power = Pd x duty cycle and check the
rise temperature : Tj = Pd x Rthj/a (Pd and Rthj/a are
given page 2)). The junction temperature must not
exceed 125°C at the maximum ambient temperature.
The maximum current is limited to the size of the
thyristors = 50A.
Ø The thermal constant (Cth) of the product is 7
minutes. That means the rise temperature is only 63%
of the stabilized temperature after a running time of
7 minutes.
45
40
35
30
1
25
20
2
15
10
5
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Tambient(°C)
fig 2
Overload current .
1 - No repetitive Itsm is given without voltage
reapplied . This curve is used for the
determination of the protection.
Fig.3 Surge current : Itsm (Apeak) = f(t) for 50A models with Itsm =550A
600
1
2 - Repetitive Itsm is given for inrush current
with initial Tj = 70°C. In normal working , this
curve musn't be exceed. Be carefull, the
repetition of the surge current decrease the
lifetime SSR's .
400
2
No repetive surge current without voltage reapplied.
200
Repetive surge current with voltage reapplied.
fig 3
0
0,01
0,1
t (s)
1
10
Mounting and dismounting on DIN rail without any tool. Panel Mounting
M5
M4
Mounting
DIN rail connected to
protection wire (ground) .
88±2mm
Dismounting
12,7mm
Ø
Warning ! semiconductor relays don't provide any galvanic insulation between the load and the mains. Always use in
conjunction with an adapted circuit breaker with isolation feature or a similar device in order to ensure a reliable isolation in the
event of wrong function and when the relay must be insulated from the mains (maintenance ; if not used for a long duration ...).
celduc
relais
www.celduc.com
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE E-Mail : celduc-relais@celduc.com
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19