DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

RUW041P7 データシートの表示(PDF) - Unspecified

部品番号
コンポーネント説明
メーカー
RUW041P7 Datasheet PDF : 20 Pages
First Prev 11 12 13 14 15 16 17 18 19 20
Characteristics (continued) Zelio Relay plug-in relays
0
Miniature relays
Relay type
Contact characteristics
Number and type of contacts
Contact materials
Conventional rated
thermal current (Ith)
For temperature T 40°C
Maximum operating rate
In operating cycles/h
No-load
Under load
Switching voltage
Minimum
Maximum
Maximum breaking capacity
RXN 21E1GGG
2 C/O
AgNI
A5
7200
3600
V5
V 400 4 , 250 6
VA 1250
RXN 41G1GGG
4 C/O
1250
Coil characteristics
Rated voltage (Un)
Average consumption
Permissible voltage variation
Drop-out voltage threshold
4 V 24…230, 50/60 Hz
6 V 12…110
4 VA 1.9
6 W 0.9
0.8…1.1 Un (50/60 Hz or 6)
4
0.15 Un
6
0.1 Un
Environment
Conforming to standards
Approvals (pending)
Ambient air temperature
around the device
Vibration resistance
Degree of protection
Shock resistance
Mechanical durability
Operating time
(response time
Electrical durability
In millions of operating cycles/h
Standard version
IEC 61 810-1
Standard version
CSA, UL
Storage
°C - 40…+ 70
Operation
°C - 20…+ 50
Conforming to
IEC 68-2-6
> 5 gn (30…150 Hz)
IP 40
20 gn
In millions of operating cycles
20
Between coil
energisation and
making of the
On-delay contact
4 ms About 12
6 ms About 12
Between coil
de-energisation and
making of the
Off-delay contacts
4 ms About 12
6 ms About 4
Resistive load
5 A / 250 V
Inductive load
See curves below
Insulation characteristics
Rated insulation voltage (Ui)
Conforming to IEC 947
Insulation class
Dielectric strength
(rms voltage)
Conforming to VDE 0110
Between coil and
4
contact
Between poles
Between contacts
4
Electrical durability of the contacts
Resistive load 4ÃÃÃ
ÃÃÃ
107
V 250
A 250
V 2000
V 2000
V 1500
Reduction coefficient for inductive load 4
(depending on power factor cos ϕ)
1
0,8
0,6
Maximum switching capacity on a resistive
load 6
$
5
4
3
2
1
106
0,7
0,4
0,5
0,4
0,3
0,2
105
0
1
2
Switching capacity (kVA)
1 0,8 0,6 0,4
0,2
Cos ϕ
0,1
0 20 40 60 80 120 160 200 250
Voltage Ã6
Durability (inductive load) = durability (resistive load) x reduction coefficient
References:
pages 28042/4 and 28042/5
Schneider Electric
Dimensions:
page 28046/2
Schemes:
page 28047/2
28042_Ver2.00-EN.fm/3

Share Link: 