Series SD
Dual Ouput to 50A 600 Vac
DC Control Solid-State Relay
ENVIRONMENTAL SPECIFICATION
Min
Max Units
Operating Temperature
–40
100
°C
Storage Temperature
–40
100
°C
Input-Output Isolation
SD24D40-06
All other relays
4000
3300
Vrms
Vrms
Output-Case Isolation
SD24D40-06
All other relays
2500
3300
Vrms
Vrms
Output to Output
SD48D50XX
All other relays
3300
2500
Vrms
Vrms
Junction-Case Thermal Resistance
SD24D40-06
All other relays
1.1 °C/W
0.5 °C/W
THERMAL CHARACTERISTICS
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
0
2 pole
1 pole
5 10 15 20 25 30 35 40 45
Load Current (Arms)
0.9°C/W
11.3.165.2°°C°CC//WW/W
2°C/W
2.6°C/W
4°C/W
Without heat sink
0 10 20 30 40 50 60 70 80 90 100 110
Ambient Temperature (°C)
Figure 6a — SD24 50A relays output current
60
55
50
45
40
35
30
25
20
15
10
5
0
0
2 pole
1 pole
111..3.625°°°C1CC°///WCWW/W
2°C/W
2.3°C/W
2.6°C/W
4°C/W
Without heat sink
5 10 15 20 25 30 35 40 0 10 20 30 40 50 60 70 80 90 100 110 120 125
Load Current (Arms)
Ambient Temperature (°C)
Figure 6b — SD24D40-06 and SD48D40-06 output current
SURGE CURRENT
600
Non-Repetitive
400
200
Repetitive with initial Tj = 70°C
0
0.01
0.1
1
10
t (s)
Figure 5a — SD24 50A output current
400
Non-Repetitive
300
200
100
Repetitive with initial Tj = 70°C
0
0.01
0.1
1
10
t (s)
Figure 5b — SD48 40A and SD24 40A output current
600
Non-Repetitive
400
200
Repetitive with initial Tj = 70°C
0
0.01
0.1
t (s)
1
10
Figure 5c — SD48 50A output current
160
0.3°C/W
140
2 pole
0.75°C/W
120
0.95°C/W
100
80
1 pole
1.6°C/W
60
2.2°C/W
40
20
6°C/W
0
0 5 10 15 20 25 30 35 40 45 50
Load Current (Arms)
0 10 20 30 40 50 60 70 80 90 100
Ambient Temperature (°C)
Figure 6c— SD48D50A and SD48D50A2 output current
NOTES:
1. Electrical specifications at 25°C unless otherwise specified.
2. For 800Hz applications, contact factory.
3. For additional/custom applications, contact factory.
OPTIONAL ADD-ONS
Please order add-ons separately:
• -12 — Thermal pad installed.
• -14 — Plastic touch-proof cover.
SD Page 4
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2016 TELEDYNE RELAYS
SD\092016\Q3