DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

LA55-TP View Datasheet(PDF) - LEM Industrial

Part Name
Description
Manufacturer
LA55-TP
LEM
LEM Industrial LEM
LA55-TP Datasheet PDF : 3 Pages
1 2 3
Current Transducer LA 55-TP
Isolation characteristics
V
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
2.5
kV
d
Vb
R.m.s. rated voltage
600
V
Min
dCp Creepage distance
6.9
mm
dCl Clearance distance
6.1
mm
CTI Comparative Tracking Index (Group IIIa)
175
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions :
Over voltage category OV 3
Pollution degree PD2
Non-uniform field
dCp, dCI
Single isolation
Reinforced isolation
EN 50178
Rated isolation voltage
600 V
300 V
IEC 61010-1
Nominal voltage
600 V
300 V
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the following
manufacturer's operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
LEM
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060126/7
Page 2/3
w w w .lem.com

Share Link: 

datasheetq.com  [ Privacy Policy ]Request Datasheet ] [ Contact Us ]