Measured Quantities
kWh total import/export
kvarh Q1, Q2, Q3, Q4
kVAh (2 calculated values)
3 customer defined registers -
summation of up to 5 values
4 inputs for external meters (if fitted)
Tariff Structure
32 Time of Use Registers
8 Maximum Demand Registers
5 Co-incident Demands
2 Sliding Demands
12 Seasons
24 Season Changeover Dates
96 Switching Times
64 Exclusion Dates
May vary according to firmware version
Programmable deferred tariff and display
Data Storage
• Programmable integration period
• Load profile storage or instrumentation quantity
• Demand & instrumentation integration periods
independently defined
Number of days (30 minute period, 1 channel)
Measured Load Profile
Instrumentation Profile
900
0
450
0
450
370
0
450
Up to 36 sets of historical data. Fully customer defined, multilingual
Input/Output
Four input module - End of billing, end of integration period, inputs
from external meters
Four output relay module - Retransmit pulses from energy
registers, customer defined registers or any time-of-use register
Option of three solid-state relays and one 5A relay or four solid-
state relays
Communications
Local:
IEC 62056-21 (formerly IEC 61107)
Remote: Interchangeable modules
(RS232, RS485 or customer specific)
Media : GSM, PSTN, Ethernet, PAKNET
Case
Sealed flip-up lid
• Conceals utility/reset pushbutton
• Provides for customers own information to be securely
added to the nameplate
• Visual identification of modules fitted
Options
• ANSI communications port
9.5 mm terminal block
Technical Data
Current Range
Reference Voltage
Frequency
Burden
Voltage Circuits (230V)
Current Circuits
Insulation
Impulse Withstand
Display
Baud Rates
Product Life
Certified Product Life
Temperature
Humidity
Pulse Width / Value
Relay Specification
Dimensions
Weight
Specifications
Case
CT operated – 5-6A, 5-10A, 1-2A, 1-1.2A
Direct connected – 10-100A (widest range)
57.5 - 240V (3 phase 4 wire)
100 - 415V (3 phase 3 wire)
50Hz or 60Hz
Single element - 1.92W, 4.17VA
Two/three element - 1.12W, 2.45VA
CT operated – 0.12VA @ 5A/phase, 0.02VA @ 1A/phase
Direct connected – 0.2VA @ 100A/phase
4kV RMS 50Hz
12kV 1.2/50µs 50ohm source
2 line, 16 character dot matrix
liquid crystal display
8mm digits
1200, 2400, 4800, 9600
15 years
10 years (by OFGEM)
-25˚ C to + 55˚ C (Operational range)
-25˚ C to + 70˚ C (Optional operating range)
-25˚ to + 70˚ C (Storage)
Annual mean 75% (for 30 days spread over one year, 95%)
Programmable
240V a.c.
100mA
1 x 5A relay (option, module only)
279mm (high) x 170mm (wide) x 81mm (deep)
1500 grams
IEC62052-11 and IEC62053-21, -22, -23
EC Directive 2004/22/EC (MID) Class A, B or C
IP53 to IEC60529:1989
Elster Metering Ltd
Tollgate Business Park
Paton Drive
Beaconside
Stafford
Staffordshire
ST16 3EF
T +44 (0)1785 275200
F +44 (0)1785 275300
www.elstermetering.co.uk