Dimensions LA 205-S (in mm. 1 mm = 0.0394 inch)
Front view
Left view
Secondary terminals
Pin 1 : supply voltage + 12 .. 15 V
Pin 2 : measure
Pin 3 : supply voltage - 12 .. 15 V
Pin 4 : NC
Connection
Top view
Mechanical characteristics
•General tolerance
•Fastening
•Primary through-hole
•Connection of secondary
Remarks
± 0.5 mm
2 holes ∅ 5.5 mm
23 x 18 mm
Molex 5046-04/AG
•IS is positive when IP flows in the direction of the arrow.
•Temperature of the primary conductor should not exceed
100°C.
•Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
•This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.