POWER
Data Sheet
Total Power: 200 - 500 Watts
Input Voltage: 85 - 264 Vac
120 - 300 Vdc
# of Outputs: Single
SPECIAL FEATURES
Active power factor correction
IEC EN61000-3-2 compliance
Remote sense
Power fail and remote inhibit
Single wire current sharing
Built-in EMI filter
Low output ripple
5 V standby
12 V fan output
Overvoltage protection
Overload protection
Thermal overload protection
DC power good
Built in OR-ing diode/FET
Optional fan cover (-CF suffix)
Optional end fan cover (-CEF suffix)
PM Bus compliant
RoHS compliant
Digital I2C interface
Two year warranty
POE isolation on NTS508
SAFETY
TUV:
cCSAus:
NEMKO:
CB:
CE:
60950
60950
60950
Certificate & report
Mark (LVD)
NTS500 Series
500 Watts
Electrical Specifications
Input
Input range
85 - 264 Vac (wide range)
Frequency
47 - 440 Hz
Inrush current
50 A max., cold start @ 25 °C
Efficiency
85% typical at full load, nominal line
EMI filter
FCC Class B conducted and radiated; CISPR22 Class B
conducted and radiated; EN55022 Class B conducted and
radiated; VDE0878PT3 Class B conducted and radiated.
Safety ground leakage current < 0.5 mA @ 50/60 Hz, 264 Vac input
Output
Maximum power
200 W for convection; 500 W with 30 CFM forced air
Adjustment range
± 5%
Standby output
5 V @ 1 A convection, 2 A forced air, regulated, ± 5%
Fan output
12 V @ 1 A, -5 %, +7%, 0.5 A for -CF version
Hold-up time
20 ms @ 500 W load, 115 VAC nominal line at factory voltage
setting
Overload protection
Short circuit protection on all outputs. Case overload
protected @ 115 - 130% above peak rating
Overvoltage protection
20 - 35% above nominal output