Industrial Power Supplies
TIS Series
75-600 Watt
Input Specifications
Input voltage range – TIS 75, TIS 150, TIS 300, TIS 600
– TIS 500
– TIS 300 DCI
93 – 132 VAC / 187 – 264 VAC
187 – 264 VAC
300 – 800 VDC
Input frequency
47 – 63 Hz
Input current at full load (typ.)
– TIS 75
– TIS 150
– TIS 300
– TIS 500
– TIS 600
115 VAC
1.7 A
3.0 A
5.4 A
10.5 A
230 VAC
0.9 A
1.7 A
3.3 A
5.5 A
6.4 A
Inrush current (< 2 ms)
– TIS 75
– TIS 150
– TIS 300
– TIS 500
– TIS 600
Output Specifications
115 VAC
< 16.5 A
< 35 A
< 35 A
< 70 A
230 VAC
< 33 A
< 70 A
< 70 A
< 70 A
< 80 A
Output voltage adj. range
– 12 VDC models
– 24 VDC models
– 28 VDC models
– 48 VDC models
– 72 VDC models
12 – 14 VDC
24 – 28 VDC
28 – 32 VDC
48 – 52 VDC (48 – 55 VDC on request))
60 – 76 VDC
Regulation – Input variation
± 0.2 % max.
– Load variation (10 – 90 %) – TIS 75, TIS 150
– TIS 300, TIS 500, TIS 600
± 1.0 % max.
± 0.3 % max.
(± 1.5 % in parallel operation)
Ripple and Noise (20MHz Bandwidth)
< 50 mV pk-pk
Electronic short circuit protection
current limitation at 110 % typ.
(constant current, automatic restart)
Overvoltage protection, triggerpoint at
140 % typ. Vout nom.
Hold-up time
– TIS 75 ... TIS 300
– TIS 500
– TIS 600
115 VAC
min. 25 ms
min. 15 ms
230 VAC
min. 30 ms
min. 40 ms
min. 25 ms
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 2